Power Requirements |
Power Consumption |
MGate MB3170: 435 mA (max.) MGate MB3170I: 555 mA (max.) MGate MB3270: 435 mA (max.) MGate MB3270I: 510 mA (max.) |
Input Voltage |
12 to 48 VDC |
Power Connector |
Terminal block |
Software |
Utilities |
MGate Manager for Windows 98/ME/NT/2000, Windows XP/2003/Vista/2008/7 x86/x64 |
Operation Modes |
RTU Slave, RTU Master, ASCII Slave, ASCII Master |
Multi-master and Multi-drop |
Master mode: 32 TCP slaves Slave mode: 16 TCP masters (request queue 32-deep for each master) |
Configuration Options |
Web Console, Serial Console, Telnet Console, Windows Utility |
Bonus Features |
Smart Routing, Serial Redirection, Priority Control |
Serial Communication Parameters |
Flow Control |
RTS/CTS, DTR/DSR (RS-232 only) |
Data Bits |
7, 8 |
Parity |
None, Even, Odd, Space, Mark |
Stop Bits |
1, 2 |
Baudrate |
50 bps to 921.6 Kbps |
Ethernet Interface |
Connector |
8-pin RJ45 |
Speed |
10/100 Mbps, Auto MDI/MDIX |
Magnetic Isolation Protection |
1.5 KV built-in |
Number of Ports |
2 (1 IP) |
Environmental Limits |
Operating Temperature |
Standard Models: 0 to 55°C (32 to 131°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity |
5 to 95% (non-condensing) |
Physical Characteristics |
Weight |
MGate MB3170: 360 g MGate MB3270: 380 g |
Dimensions |
Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in) With ears extended: 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in) |
Housing |
Plastic |
Serial Interface |
Connectors |
MB3170/3170I: DB9 male for RS-232, Terminal block for RS-422/485 MB3270/3270I: DB9 male x 2 |
Serial Standards |
RS-232/422/485, software selectable |
RS-485 Data Direction Control |
ADDC® (automatic data direction control) |
ESD Protection |
15 KV for all signals |
Number of Ports |
MB3170/3170I: 1 MB3270/3270I: 2 |
Pull High/Low Resistor for RS-485 |
1 KΩ, 150 KΩ |
Terminator for RS-485 |
120 Ω |
Reliability |
MTBF (mean time between failures) |
MGate MB3170: 210,794 hrs MGate MB3270: 125,234 hrs |
Serial Signals |
RS-485-4w |
Tx+, Tx-, Rx+, Rx-, GND |
RS-485-2w |
Data+, Data-, GND |
RS-422 |
Tx+, Tx-, Rx+, Rx-, GND |
RS-232 |
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
Standards and Certifications |
EMI |
EN 55022 Class A, FCC Part 15 Subpart B Class A |
Safety |
UL 60950-1, EN 60950-1 |
Hazardous Location |
UL/cUL Class I Division 2 Groups A/B/C/D, ATEX Zone 2 |
Shock |
IEC 60068-2-27 |
Vibration |
IEC 60068-2-6 |
EMS |
EN 55024, EN 61000-4-2 (ESD) Level 3, EN 61000-4-3 (RS) Level 3, EN 61000-4-4 (EFT) Level 4, EN 61000-4-5 (Surge) Level 3, EN 61000-4-6 (CS) Level 3, EN 61000-4-8, EN 61000-4-11, EN 61000-4-12 |
EMC |
CE, FCC |
Freefall |
IEC 60068-2-23 |
Marine |
DNV |
Warranty |
Warranty Period |
5 years |
Details |
See www.moxa.com/warranty |